How can we help?
Note: This configuration is only able to be enabled by Pelican technical support.
For Hot Water or Steam Floating Valve Control: Wire the thermostat’s (W) output to open the valve and (W2) to close the valve.
For Chilled Water Valve Control: Wire the thermostat’s (Y) output to open the valve and (Y2) to close the valve.
This configuration is found under: Admin > Thermostat’s configuration > “select any thermostat” > Thermostat Operation > Floating Valve (hidden configuration).
Note: This configuration is only able to be enabled by Pelican technical support.
Face and Bypass Damper Actuator Wiring: Wire the thermostat’s (W) output to place the damper to the coil’s Face and (W2) to place the damper to Bypass the coil.
This configuration is found under: Admin > Thermostat’s configuration > > “select any thermostat” > Variable Temperature Control.
Note: This configuration is only available if the thermostats is configured to communicate with a Pelican Z8 or Z24.
This configuration is found under: Admin > Thermostat Configuration > “select any thermostat” > System Type set to Zone Damper > Zone Controller = “select the zone controller the thermostat communicates with” > Damper Settings > Damper Type = Floating
Floating Damper: You will need to set the following configurations.
Note: This configuration is only available if the thermostats is configured to communicate with a Pelican Z8 or Z24.
This configuration is found under: Admin > Thermostat Configuration > “select any thermostat” > System Type set to Zone Damper > Zone Controller = “select the zone controller the thermostat communicates with” > Damper Settings > Reheat Type = Floating
Floating Reheat: You will need to set the following configurations.