How much data does the Pelican Solution use?

How much data does the Pelican Solution use? So low you will not be able to measure it on your network. A single Pelican thermostat, which has the highest data usage, generates about 5 megabytes of traffic per month. This is equivalent to around 0.15 bytes per second OR 0.00000015 megabytes per second. In other […]

What should I set Notification Settings to?

What should I set Notification Settings to? There are three configurations under Notification Settings, this section goes over each configuration: Sensitivity To generate an automated cooling or heat failure notification, two things need to happen: The room’s temperature is not moving in the correct direction, during an active heating or cooling cycle, compared with an hour […]

What should I set Reheat Type to?

What should I set Reheat Type to? This configuration is only available for sites that have Pelican Zone Controllers (Z8 or Z24) and thermostats that have System Type set to Single Duct Damper. Reheat Type This configuration is found under: Admin > Thermostat Configuration > “select any thermostat” > System Type set to Zone Damper > Zone […]

What should I set Damper Type to?

What should I set Damper Type to? This configuration is only available for sites that have Pelican Zone Controllers (Z8 or Z24) and thermostats that have System Type set to Single or Dual Duct Damper. Damper Type This configuration is found under: Admin > Thermostat Configuration > “select any thermostat” > System Type set to Zone […]

What should I set Fan Purge Cycle to?

What should I set Fan Purge Cycle to? This configuration is only settable by Pelican Technical Support. Fan Purge Cycle is used to adjust how long a thermostat keeps the fan enabled after a heating and cooling cycle. A Purge Cycle is used to push any latent energy out of the air handler and into […]

What should I set a thermostat’s Zone Controller configuration to?

What should I set a thermostat’s Zone Controller configuration to? The following configurations are only available if there is a Pelican Zone Controller (Z8 or Z24) part of your Pelican Solution: Zone Controller For a Pelican Zoning Solution, each thermostat controls its own zone damper and requests Heating, Cooling, and Ventilation for a Pelican Zone […]

When would I disable the thermostat’s internal sensor?

When would I disable the thermostat’s internal sensor? In some situations the Pelican master thermostat might be installed in a room or in a location completely isolated from where it is maintaining temperature. In this scenario, you will want to use an external sensor (wired or wireless) and set the thermostat’s internal sensor to disabled. […]

When should I use the thermostat Calibration Degrees?

When should I use the thermostat Calibration Degrees? Rarely. All Pelican thermostats come with extremely accurate, factory calibrated, room temperature sensors. What are the configuration options? 0°F (default): Leaving Calibration Degrees at 0°F keeps the thermostat using its factory calibrated temperature readings. 0.5 °F to 2.0 °F: The thermostat will read warmer in the room […]

When is Fan Circulation Minutes​ used?

When is Fan Circulation Minutes​ used? Fan Circulation Minutes enforces a minimum fan run-time for each hour of the day. What are common uses for Fan Circulation Minutes? During occupied hours you can use this configuration to make sure the fan runs for a minimum number of minutes every hour to provide proper indoor ventilation. […]

What voltage floating actuators can a Pelican thermostat control?

What voltage floating actuators can a Pelican thermostat control? 24 Vac floating actuators. A Pelican thermostat can control hot water, steam, chilled water, zone damper, and/or zone reheat 24 Vac floating actuator. Contact Pelican Sales and ask for sales engineer support for your application. Note: If you have a line-voltage (120 Vac, 240 Vac, or […]