The TCM1 is used in two distinct applications:
1. In a hotel rooms with a PTAC unit, which does not require a wire to connect it to a thermostat.
2. In zoned applications where a room has, or is installing, 24 VAC damper actuators and currently does not or cannot have wire run between the actuator and a thermostat.
Wireless 24VAC Controller (TCM1)
_
_
_
Hotel Wireless PTAC Control
In the unique situation where no wire is available or wire cannot be run between a PTAC and thermostat - install the TCM1 as a 24 VAC PTAC controller. A Pelican RT1-DC wireless remote thermostat can be installed in the same space to wirelessly tell the TCM1 when to energize the PTAC.
Wireless Damper Actuator Control
In the unique scenario where no wire is available or wire cannot be run between a 24VAC damper actuator and Pelican thermostat - install a TCM1 to control a 24 VAC actuator. A Pelican RT1-DC wireless remote thermostat can be installed in the same space to wirelessly tell the TCM1 when to open and close the actuator.
_
_
_
Automated Wireless Connection
Because we integrate our advanced wireless mesh network into every thermostat, there is ZERO wireless setup required. No passwords to enter or complex connection processes to go through. Thermostats automatically connect to each other and back to the Pelican Gateway (GW400). Easy plug and play technology with no WiFi interference or requirement.


_



Online Management
The TCM1 automatically connects wirelessly to a Pelican Wireless Gateway (GW400) installed at the customer's site. Now you can manage all configuration, scheduling, and system operation right from your smartphone, tablet, or PC. Complete control at your fingertips no matter where you are.
Alarm Notifications
Every TCM1 (when connected to a Pelican Remote Wireless Sensor) monitors building space temperature in real-time. Using advanced diagnostic and reporting capabilities, the TCM1 lets you know when your HVAC system fails. Now you can quickly determine the issue and resolve the problem.
Controlled User Access
Administrators have complete control over thermostats and can add or delete other Administrators or Users to the Pelican Web App. Administrators manage Users through settable restrictions fr the type of control allowed over the thermostats in your building. This gives the ultimate flexibility over who can control what.



Easy Installation
The TCM1 installs the same way as any stand-alone programmable thermostat. It connects to the HVAC unit using standard thermostat wire. The TCM1 can control the HVAC unit for up to 2H/2C Conventional or 3H/2C Heat Pump. Or, it can control 24 VAC actuators for zoned systems.

Energy Efficiency
With Internet connection you have real-time information based on exactly how every thermostat is operating in your building. You can create schedules for managing each building spaces or create Group Schedules to share between multiple thermostats. With real control right at your fingertips, saving money and increasing comfort is now simple and efficient.

Historical Trend Data
Every TCM1 tracks trend data in real-time so you can visually see exactly how your spaces are operating at any moment of the day. This data is accessible Online for up to 2 years for every thermostat. The TCM1 also tracks Usage Data, so you can se how much energy is allocated to just the HVAC vs. other building electrical loads.
TCM1
Hardwire: 24VAC, 60Hz; 50mA
Voltage Rating: 23 - 30VAC
Relay Current: 1.0A running
_
Power
Wiring
Size
Conventional Unit
R: 24VAC
C: Neutral
Rc: 2nd 24VAC Transformer
Y: 1st Stage Cool
W: 1st Stage Heat
Y2: 2nd Stage Cool
W2: 2nd Stage Heat
G: Fan
Heat Pump Unit
R: 24VAC
C: Neutral
Rc: 2nd 24VAC Transformer
Y: 1st Stage Compressor
W: (O/B) Reversing Valve
Y2: 2nd Stage Compressor
W2: AUX Heat
G: Fan
Single Duct Damper Actuator
R: 24VAC
C: Neutral
Rc: 2nd 24VAC Transformer
Y: 24VAC Damper Open
W: 24VAC Reheat
Y2 - 24VAC Damper Close
Duel Duct Damper Actuator
R: 24VAC
C: Neutral
Rc: 2nd 24VAC Transformer
Y: 24VAC Cool Damper Open
W: 24VAC Heat Damper Open
Y2: 24VAC Cool Damper Close
W2: 24VAC Heat Damper Close

Height: 5.9 inch (150 mm)
Width: 3.5 inch (89 mm)
Depth: 1.5 inch (38 mm)
TCM1 Range
Operating Range: -4 deg. F to 122 deg. F
Differential Temperature: +/- 0.5 deg. F
Operating Humidity (% RH): 5 to 90%; non-condensing
Storage Temperature: -20 deg. F to 160 deg. F
System Protection
Four Minute Compressor Short Cycle Protection
Temporary Schedule Override
Thermostat Keypad Lockout
Trend Data Analytic and Fault Monitoring
Auxiliary/Emergency Heat Efficiency Algorithm
WirelessThermostats
24VAC Powered

Battery Powered
RT1-AC
RT1-DC