TCM1image

The TCM1 is used in two distinct applications:

 

1. In a hotel rooms with a PTAC unit, which does not require a a wire to connect it to a thermostat.

 

2. In zoned applications where a room has, or is installing, 24 VAC damper actuators and currently does not or cannot have wire run between the actuator and a thermostat.

Wireless 24VAC Controller (TCM1)

_

_

_

Hotel Wireless PTAC Control

In the unique situation where no wire is available or wire cannot be run between a PTAC and thermostat - install the TCM1 as a 24 VAC PTAC controller. A Pelican RT1-DC wireless remote thermostat can be installed in the same space to wirelessly tell the TCM1 when to energize the PTAC.

Wireless Damper Actuator Control

In the unique scenario where no wire is available or wire cannot be run between a 24VAC damper actuator and Pelican thermostat - install a TCM1 to control a 24 VAC actuator. A Pelican RT1-DC wireless remote thermostat can be installed in the same space to wirelessly tell the TCM1 when to open and close the actuator.

_

_

_

Automated Wireless Connection

Because we integrate our advanced wireless mesh network into every thermostat, there is ZERO wireless setup required. No passwords to enter or complex connection processes to go through. Thermostats automatically connect to each other and back to the Pelican Gateway (GW400). Easy plug and play technology with no WiFi interference or requirement.

thermostatwireless2
ThermostatFront

_

TCM1image
tcm1damper
onlinemanagement

Online Management

 

The TCM1 automatically connects wirelessly to a Pelican Wireless Gateway (GW400) installed at the customer's site. Now you can manage all configuration, scheduling, and system operation right from your smartphone, tablet, or PC. Complete control at your fingertips no matter where you are.

Alarm Notifications

 

Every TCM1 (when connected to a Pelican Remote Wireless Sensor) monitors building space temperature in real-time. Using advanced diagnostic and reporting capabilities, the TCM1 lets you know when your HVAC system fails. Now you can quickly determine the issue and resolve the problem.

Controlled User Access

 

Administrators have complete control over thermostats and can add or delete other Administrators or Users to the Pelican Web App. Administrators manage Users through settable restrictions fr the type of control allowed over the thermostats in your building. This gives the ultimate flexibility over who can control what.

alarmnotifications3
securelockicon2
gearsicon

Easy Installation

 

The TCM1 installs the same way as any stand-alone programmable thermostat. It connects to the HVAC unit using standard thermostat wire. The TCM1 can control the HVAC unit for up to 2H/2C Conventional or 3H/2C Heat Pump. Or, it can control 24 VAC actuators for zoned systems.

ecogreen

Energy Efficiency

 

With Internet connection you have real-time information based on exactly how every thermostat is operating in your building. You can create schedules for managing each building spaces or create Group Schedules to share between multiple thermostats. With real control right at your fingertips, saving money and increasing comfort is now simple and efficient.

historygraph

Historical Trend Data

 

Every TCM1 tracks trend data in real-time so you can visually see exactly how your spaces are operating at any moment of the day. This data is accessible Online for up to 2 years for every thermostat. The TCM1 also tracks Usage Data, so you can se how much energy is allocated to just the HVAC vs. other building electrical loads.

TCM1

Hardwire: 24VAC, 60Hz; 50mA

Voltage Rating: 23 - 30VAC

Relay Current: 1.0A running

_

Power

Wiring

Size

Conventional Unit 

R: 24VAC

C: Neutral

Rc: 2nd 24VAC Transformer

Y: 1st Stage Cool

W: 1st Stage Heat

Y2: 2nd Stage Cool

W2: 2nd Stage Heat

G: Fan

Heat Pump Unit 

R: 24VAC

C: Neutral

Rc: 2nd 24VAC Transformer

Y: 1st Stage Compressor

W: (O/B) Reversing Valve

Y2: 2nd Stage Compressor

W2: AUX Heat

G: Fan

Single Duct Damper Actuator

R: 24VAC

C: Neutral

Rc: 2nd 24VAC Transformer

Y: 24VAC Damper Open

W: 24VAC Reheat

Y2 - 24VAC Damper Close

Duel Duct Damper Actuator

R: 24VAC

C: Neutral

Rc: 2nd 24VAC Transformer

Y: 24VAC Cool Damper Open

W: 24VAC Heat Damper Open

Y2: 24VAC Cool Damper Close

W2: 24VAC Heat Damper Close

TCM1-size

Height: 5.9 inch (150 mm)

Width: 3.5 inch (89 mm)

Depth: 1.5 inch (38 mm)

 

TCM1 Range

Operating Range: -4 deg. F to 122 deg. F

Differential Temperature: +/- 0.5 deg. F

Operating Humidity (% RH): 5 to 90%; non-condensing

Storage Temperature: -20 deg. F to 160 deg. F

 

System Protection

Four Minute Compressor Short Cycle Protection

Temporary Schedule Override

Thermostat Keypad Lockout

Trend Data Analytic and Fault Monitoring

Auxiliary/Emergency Heat Efficiency Algorithm

 






document

Installation Instructions 

_

Product Specification

document

Alternative text - include a link to the PDF!

WirelessThermostats

24VAC Powered

ts200-bubble

Battery Powered

RT1-AC

RT1-DC

ts200-bubble